Download PDF version

The requirement to save energy often leads to the installation of larger air handling units, which in turn results in lower airflow velocities. It is, therefore, necessary to change the measurement principle in order to measure even very small volume flows.

Another issue often encountered at the installation site is space or the lack of it. This is why development efforts have to aim at products that are fairly easy and safe to install and provide good measurement results.

With these goals in mind, TROX has developed a new measurement method and a new type of damper blade, for which a patent application has already been filed. The new damper blade is part of the new VAV terminal units, Type TVE.

Design

Type TVE VAV terminal units apply a new measurement principle as the volume flow rate is measured not with a probe or sensor, but by means of the damper blade itself. This innovative design allows for a reduction in length and helps to ensure precise measurement results even in the case of unfavorable upstream conditions; with dynamic measurement, this is even independent of the airflow direction.

Advantages

  • Works perfectly even with unfavorable upstream conditions
  • The relation between damper blade position and differential pressure is stored as a characteristic relationship in the controller
  • Higher measurement accuracy even with low airflow velocities from 0.5 m/s
  • Nominal sizes of 100, 125, 160, 200, 250 mm
  • Volume flow rates of 14 m³/h – 2300 m³/h (4 l/s – 640 l/s)
  • Volume flow rate range of 1:25
  • Choice of the static or dynamic transducer
  • Available with Easy controller, Compact controller, or Modbus RTU variant for connection to the central BMS
  • Airflow direction is not critical if dynamic measurement is used
  • Release button on control component allows for easy replacement of the component
Download PDF version Download PDF version

In case you missed it

2025 AHR Expo: Top Innovations In HVACR Announced
2025 AHR Expo: Top Innovations In HVACR Announced

The AHR Expo (International  Air-Conditioning, Heating, Refrigerating Exposition) today announced the winners of the 2025 AHR Expo Innovation Awards. Winners are chosen annua...

Johnson Controls Center Develops And Tests HVAC Systems For Data Centers
Johnson Controls Center Develops And Tests HVAC Systems For Data Centers

Johnson Controls’ Advanced Development Engineering Center (JADEC) in New Freedom, PA., about 25 miles from Philadelphia, highlights and demonstrates the company’s capab...

Airzone Aidoo Pro Enhances VRF Energy Efficiency
Airzone Aidoo Pro Enhances VRF Energy Efficiency

The Olsen Group, based in Boca Raton, Florida, is a national pioneer in HVAC energy optimization. Donald Olsen and his seasoned team of HVAC control specialists have been in busine...

vfd