The location where a sensor is placed is critical in the function of a good heat trace system. Contractors or installers seldom own the facility where they install a system. If they did own it, they might stop and think a little more often about where the actual best place to install a sensor would be when they built the heat trace system, wouldn’t they?

The best place to have a sensor is always where the temperature is most critical. Heat trace circuits can be anywhere from ten feet to hundreds of feet long. But where along any given run is the most important place for the content of that pipe to be at temperature? First, let’s define two important terms: line sensing and ambient sensing. 

What is line sensing?

Line sensing is when temperature sensors are located on the surface of the product being controlled.

What is ambient sensing?

Both ambient sensing and line sensing have their advantages and disadvantages

Ambient sensing is when temperature sensors measure air temperature and decide what outside air temperature would be appropriate to turn a heat trace system on to protect that process.

Both ambient sensing and line sensing have their advantages and disadvantages. Let’s take a deeper look to see which type of temperature measurement sensor system would work best for user applications.

Ambient sensing

Ambient sensing applications tend to be freeze protection applications. Having a sensor outside that can tell when temperatures are close to freezing signals the heat trace system to apply power to the individual circuits to begin heating, preventing the contents of that pipe or vessel from freezing.

Normally there is just one sensor for the entire system. A user could have one sensor telling dozens of circuits to come on all at once. These are very simple control systems and can be very effective if installed properly. 

Problems with ambient sensing

So what could go wrong with ambient-controlled systems?  Here are a few things to consider:

  • Having just one sensor does not give users good insurance. If the sensor fails, the user has no temperature measurement to make a decision with. Investing in a secondary or backup sensor for the user system is a wise precaution.
  • The location of the sensor is a very common issue when troubleshooting a heat trace system with ambient sensing. Some of the more simple systems include a very old-fashioned thermostat with a mercury-filled bulb and capillary that is attached right to the thermostat. If that thermostat and sensor are placed somewhere that cannot feel cold ambient temperature, it may be too late for the system to engage. These sensors are often at the “Man Level” as well, where things get kicked, knocked off, or otherwise damaged. Putting a sensor high up in the air and away from possible mechanical damage (usually on the north side of the facility) is a smart improvement for ambient temperature systems. This often requires slight changes in the controller and sensor, for which an NPT LB-mounted style RTD is a great option. The RTD can be mounted in a standard ½” FNPT(Insert pic of the PT RTD) LB fitting to conduit, then the 3 conductor RTD wire can be run back to the controller. This controller can then actuate the control panel as originally designed.

What is line sensing?

Line-sensing heat trace systems have the sensor placed on the surface of the system

Line sensing heat trace systems have the sensor placed on the surface of the system needing to be maintained. It is common for multiple pipes or vessels on the same heat trace control system to have many circuits with each individual line having its own different required control temperature. 

Just as with ambient temperature sensing systems, where line sensors are placed is vital in the performance of the system.

Sensor Location

Engineering drawings will often have the sensors placed randomly with no consideration of that sensor location. Contractors often place sensors where it’s convenient to locate them (for example, in close proximity to a power drop).

While it’s convenient to run conduit and power wires and “drop” to equipment requiring that power, locating a sensor at that same location is not always the most optimal location for a process 

Line Sensing In Piping 

For piping, attaching the sensor to the pipe mechanically is key to long-term reliability. An RTD like this attaches to the pipe surface with a pipe clamp and then is insulated. Many clients prefer to measure the temperature at the end of a piping run so that it is at the proper temperature once it reaches its destination.

There are systems available that can measure temperature at multiple locations along a run if this is required. Placing multiple RTDs or Thermocouples along that pipe run, as well as having a controller that can monitor temperature, manage data and make a decision for heat output, would also be needed. 

Line sensing in vessels

Users want to be touching the surface of that vessel since the user is depending on it to transfer the heat

For vessels, consider if it is a horizontal or vertical tank. Heat rises, so it is common to have more electric heat trace on the bottom runs than on the top. Stacking user sensors perpendicular to the ground so that the zones can turn on and off as the heat rises would be much more effective.

Make sure that the sensor is touching the surface of the tank. Banding clamps are often used to fix the sensor in place, and in some cases, mechanical attachments are also used. Users want to be touching the surface of that vessel since the user is depending on it to transfer the heat to the product in the tank.

Line sensing in valves and pumps

It’s also important to consider critical pumps and valves in a line sensing application. If users have a valve or pump that is going to require more service than anything else on that individual heat trace circuit, think about making some modifications.

  • If users are using removable insulation blankets for that pump or valve, what about having a separate heat trace circuit for just that unit? That way, the rest of the heat trace for that pipe run is not dependent on how well someone replaces that jacket or heat trace once the maintenance is done. It’s very common for a valve or pump to be worked on or replaced, and then the heat trace or insulation jacket does not get put back on correctly. Making a separate circuit just for that critical part could be the answer.
  • Consider using a Powerblanket heated jacket for that valve or pump. With up to 10x as much heat capability vs heat trace over the same surface area, more effective heat can be useful. Being able to remove an insulation jacket with integrated heat inside the blanket all in one shot can also be a big plus. With Powerblanket, there’s no wrangling heat trace cable and trying to put it back on just right.

Is line sensing better than ambient sensing?

There is a strong argument that all applications should be line sensing. Think about a freeze protection system for piping as an example. If it is 35F outside, and the pipe under the insulation is still at 45F, the user has 12 degrees to go before it freezes.

Line sensing is much more effective and probably a better use of electricity as well. This type of system requires a more complex control system, but the savings in electricity over time on a large system would quickly pay for itself. Turning things on at 45F isn’t a bad idea if users live in a consistently cold climate.

Download PDF version Download PDF version

In case you missed it

2025 AHR Expo: Top Innovations In HVACR Announced
2025 AHR Expo: Top Innovations In HVACR Announced

The AHR Expo (International  Air-Conditioning, Heating, Refrigerating Exposition) today announced the winners of the 2025 AHR Expo Innovation Awards. Winners are chosen annua...

Johnson Controls Center Develops And Tests HVAC Systems For Data Centers
Johnson Controls Center Develops And Tests HVAC Systems For Data Centers

Johnson Controls’ Advanced Development Engineering Center (JADEC) in New Freedom, PA., about 25 miles from Philadelphia, highlights and demonstrates the company’s capab...

Airzone Aidoo Pro Enhances VRF Energy Efficiency
Airzone Aidoo Pro Enhances VRF Energy Efficiency

The Olsen Group, based in Boca Raton, Florida, is a national pioneer in HVAC energy optimization. Donald Olsen and his seasoned team of HVAC control specialists have been in busine...

vfd