Download PDF version

Plastic Hebert is a producer of injection moulded plastic packaging for the food industry, with a wide-ranging client portfolio that includes small manufacturers and multi-national blue chip companies.

A comprehensive air audit, conducted by AIRMATICS™ and INOV, at the firm’s plant in Orgelet, France, revealed that over 20 percent of energy relating to its air compressors was being wasted.

As a company committed to environmentally responsible manufacturing and minimizing its carbon footprint, Plastic Hebert turned to AIRMATICS™ to devise a solution that would cut wastage, reduce its energy bill and deliver long-term sustainability gains.

The project

AIRMATICS™ and INOV monitored Plastic Hebert’s compressors and compressor room over a five-day period, which confirmed the presence of air leakages, how electricity was being wasted and that the system’s average operating pressure of 7.5 bar was over 30 percent higher than required.

Unload running was also hugely inefficient, with three compressors being used on weekdays and as much as 40 percent of electricity being wasted at weekends.

Combating the challenge

AIRMATICS™ and INOV devised a solution that would align output with demand

To combat this, AIRMATICS™ and INOV devised a solution that would align output with demand by incorporating an air compressor performance, monitoring, and control system that enabled pressure sensors to be installed in each of the three compressor rooms to provide the capability to carefully balance pressure. This step facilitated effective unload running with only one compressor during the week.

Variable Speed Drives were also retrofitted to one of the compressors to continually measure demand and accurately regulate output at a consistent predetermined pressure.

The inclusion of remote monitoring technology by AIRMATICS™ also allowed Plastic Hebert to identify areas where further savings could be made, such as the reconfiguring of their system’s pipe network – a move that is expected to save the firm €10,000.

The result

By integrating the range of solutions available through AIRMATICS™ Plastic Hebert has:

  • Saved a total of over €30,000 per annum on energy bills
  • Reduced energy consumption by up to 40 Wh/Nm3 per year, which has also significantly decreased its carbon footprint
  • Taken weekday unload running down from three compressors to one compressor – a saving €15,000 each year alone
  • Identified the opportunity to save €10,000 per year by reconfiguring its pipework and minimizing pressure differentials

Clear visibility

We now have clear visibility of our daytime, night-time and weekend compressed air requirements and can adjust output accordingly. We are also able to maintain system pressure consistently across our factory, removing the disruptions that were previously caused by machinery downtimes.”

The improvements implemented should pay for themselves within twelve months and we are absolutely delighted with the production, energy saving, and cost reduction benefits that are now being delivered,” stated David Ligonesche, Plastic Hebert.

Download PDF version Download PDF version

In case you missed it

Johnson Controls On Financial Times Europe Climate Leaders List
Johnson Controls On Financial Times Europe Climate Leaders List

Johnson Controls, the global pioneer for smart, healthy and sustainable buildings, has again been named to the Financial Times Europe Climate Leaders list in 2024. This marks...

How Finalized SNAP Rule 26 Will Impact Uses Of Commercial Refrigerants
How Finalized SNAP Rule 26 Will Impact Uses Of Commercial Refrigerants

SNAP Rule 26 marks an important milestone in the transition from commercial refrigeration to new refrigerants. The rule lists refrigerant substitutes that provide a spectrum of tec...

Carrier Cooling-As-A-Service For Enhanced HVAC Solutions
Carrier Cooling-As-A-Service For Enhanced HVAC Solutions

Carrier is pleased to announce Carrier Cooling-as-a-Service, a portfolio of innovative solutions to help commercial customers simplify the operation of HVAC and other thermal or el...

vfd