Carrier 39DC-500 Double-wall Data Center Air Handler

Technical Specification

Features:
  • Make: Carrier
  • Model code: 39DC-500
  • Filters: MERV
  • Quantity: 62,900 CFM
  • Placement: Indoor/Outdoor
Read more
Additional info:

Draw thru configuration Direct drive airfoil blade fans with premium efficiency variable speed EC Motors MERV 8 filters Aluminum fin cooling coil: 0.020” copper tubes and 0.075” aluminum fins 16 GA double wall construction - max leakage 1% at 6” W.C. pressure Max deflection L/240 Single point piping connection Custom color available (black is standard) All service access from front of unit

Read more
Make Carrier
Manufacturer Carrier Corporation
Category Cooling>Air Handling Units
Model code 39DC-500
Filters MERV
Quantity 62,900 CFM
Placement Indoor/Outdoor
Speed Variable
Depth 60 inches
Width 168 inches
Height 168 inches
Additional info
  • Draw thru configuration
  • Direct drive airfoil blade fans with premium efficiency variable speed EC Motors
  • MERV 8 filters
  • Aluminum fin cooling coil: 0.020” copper tubes and 0.075” aluminum fins
  • 16 GA double wall construction - max leakage 1% at 6” W.C. pressure
  • Max deflection L/240
  • Single point piping connection
  • Custom color available (black is standard)
  • All service access from front of unit
Download PDF version Download PDF version
vfd